Cooling Water - Pipe Lines
Sponsored Links
Main Pipes - maximum allowable flow, velocity and pressure drop
Cooling Water - Main PipesPipe Size (in) | Flow | Velocity | Pressure Drop | |||
---|---|---|---|---|---|---|
(US gpm) | (liter/s) | (ft/s) | (m/s) | (ftH2O/100 feet) | (Pa/100 m) | |
4 | 140 | 9 | 3.5 | 1.1 | 2.2 | 21827 |
6 | 380 | 24 | 4.2 | 1.3 | 1.9 | 18877 |
8 | 650 | 41 | 4.2 | 1.3 | 1.4 | 13371 |
10 | 1100 | 69 | 4.2 | 1.3 | 1.2 | 11700 |
12 | 1800 | 114 | 4.5 | 1.4 | 1.2 | 12093 |
14 | 2200 | 139 | 5.1 | 1.6 | 1.1 | 11208 |
16 | 3300 | 208 | 5.9 | 1.8 | 1.2 | 11405 |
18 | 4500 | 284 | 6.2 | 1.9 | 1.2 | 11503 |
20 | 6000 | 379 | 6.7 | 2.0 | 1.2 | 11503 |
24 | 11000 | 694 | 7.8 | 2.4 | 1.2 | 11700 |
30 | 19000 | 1199 | 8.7 | 2.6 | 1.1 | 10913 |
3 | 70 | 4 | 3.0 | 0.9 | 2.3 | 22712 |
Lateral Pipes - maximum allowable flow, velocity and pressure drop
Cooling Water - Lateral PipesPipe Size (in) | Flow | Velocity | Pressure Drop | |||
---|---|---|---|---|---|---|
(US gpm) | (liter/s) | (ft/s) | (m/s) | (ftH2O/100 feet) | (Pa/100 m) | |
4 | 200 | 13 | 5.1 | 1.5 | 4.3 | 42179 |
6 | 500 | 32 | 5.6 | 1.7 | 3.2 | 31364 |
8 | 900 | 57 | 5.8 | 1.8 | 2.5 | 24383 |
10 | 1500 | 95 | 6.1 | 1.9 | 2.1 | 20745 |
12 | 2400 | 151 | 6.8 | 2.1 | 2.1 | 20647 |
14 | 3100 | 196 | 7.2 | 2.2 | 2.1 | 20647 |
16 | 4500 | 284 | 7.9 | 2.4 | 2.1 | 20549 |
18 | 6000 | 379 | 8.3 | 2.5 | 2.0 | 19565 |
3 | 100 | 6 | 4.3 | 1.3 | 4.5 | 43949 |
Sponsored Links
Related Topics
• Piping Systems
Calculate dimensions of pipes and tubes. Pressure drop calculations and head loss charts. Use of different piping materials. Insulation of pipes and tubes and heat loss diagrams.
Related Documents
Calculating Cooling Loads
Calculating chiller and cooling tower refrigeration loads - in tons.
Chilled Water Systems
Chilled water system equations - evaporator and condenser flow rates.
Cooling Tower Efficiency
Maximum cooling tower efficiency is limited by the cooling air wet-bulb temperature.
Insulation of Cooling Systems
Cooling systems and insulation thickness.
Water - Absolute (Dynamic) Viscosity vs. Temperature and Pressure
Absolute viscosity for water in centipoises for temperatures between 32 - 200oF.
Water Systems - Maximum Flow Velocities
Water velocities in pipes and tubes should not exceed certain limits.
Sponsored Links
Search Engineering ToolBox
Search is the most efficient way to navigate the Engineering ToolBox!
Privacy
We don't collect information from our users. Only emails and answers are saved in our archive. Cookies are only used in the browser to improve user experience.