Relative Humidity in Production and Process Environments

Recommended relative humidity in production and process environments - like libraries, breweries, storages and more.

Environment and indoor climate must often be within certain temperature and humidity limits to avoid deterioration and damage of products or to achieve proper process conditions.

To low relative humidity may dry up products and to high relative humidity may increase the "water activity" and the growing of mold and bacteria in process lines and their products.

  • bacteria need in general more than 90% relative humidity to grow
  • mold need in general more than 80% relative humidity to grow

The exact water activity limit for a specific organism depends on other factors such as pH, oxygen availability, the nature of the solutes present, nutrient availability and temperature. 

Recommended relative humidity for some common production and product process are indicated in the table below.

Relative Humidity in Production or Process Environments
Production or Process EnvironmentRecommended Relative Humidity
- RH -
(%)
Sugar Storage 20 - 35%
Breweries 35 - 45%
Coffee Powder 30 - 40%
Milk Powder Storage 20 - 35%
Seed Storage 35 - 45%
Unpacked Medicine 20 - 35%
Transformer Winding 15 - 30%
Semiconductors 30 - 50%
Books and Paper Archive 40 - 55%
Paper Storage 35 - 45%
Preventing Rust and Corrosion below 55%,
< 40% for no rust generation
Library 50 - 55%
Spray Paint 30 - 50%
Laboratory electronics 45 - 60%
Plastic Pallets 5 - 30%
Computer Peripherals 50 - 60%
Rust Resistance Below 40%
Medical Syrups 30 - 40%
Capsule Storage 30 - 45%
Powder Storage 30 - 45%
Wood Drying 25 - 35%
Explosives 35 - 50%
Note!
low RH may generate static electricity and spark ignitions
Normal Storage 50 - 55%
Musical Instrument 45 - 55%
Leather Product 40 - 55%
Cable Wrapping 15 - 25%
Chemical Laboratory 30 - 45%

Related Topics

  • Air Conditioning Systems

    Design of Air Conditioning systems - heating, cooling and dehumidification of indoor air for thermal comfort.
  • Air Psychrometrics

    Moist and humid air calculations. Psychrometric charts and Mollier diagrams. Air-condition systems temperatures, absolute and relative humidities and moisture content in air.
  • Ventilation Systems

    Design of systems for ventilation and air handling - air change rates, ducts and pressure drops, charts and diagrams and more.

Related Documents

Our Mission

The Engineering ToolBox provides a wide range of free tools, calculators, and information resources aimed at engineers and designers. It offers detailed technical data and calculations for various fields such as fluid mechanics, material properties, HVAC systems, electrical engineering, and more.

The site includes resources for common engineering tasks, such as calculating physical properties (e.g., density, viscosity, thermal conductivity), converting units, and designing systems like heating and water distribution.

With sections on everything from acoustics to hydraulics, it serves as a comprehensive tool for both students and professionals in technical and engineering disciplines.

About the Engineering ToolBox!

Privacy Policy

We don't collect information from our users. More about

We use a third-party to provide monetization technology for our site. You can review their privacy and cookie policy here.

You can change your privacy settings by clicking the following button: .

Citation

This page can be cited as

  • The Engineering ToolBox (2003). Relative Humidity in Production and Process Environments. [online] Available at: https://www.engineeringtoolbox.com/relative-humidity-production-process-d_511.html [Accessed Day Month Year].

Modify the access date according your visit.